Siemens PXC36.1.D Desigo PX Compact Automation Station
Product Overview
The Siemens PXC36.1.D (Stock No. S55372-C120) is a high-performance, compact direct digital control (DDC) automation station belonging to the Desigo PX system family.
Designed for HVAC and building services automation, the PXC36.1.D features a fixed physical layout of 36 integrated I/O data points. The “.1” designation indicates that it includes an Island Bus interface, allowing local I/O expansion using TX-I/O modules or TX Open integrations. It operates using native BACnet on LonTalk network protocols for peer-to-peer and supervisory communication.
Technical Specifications
| Parameter | Specification Details |
|---|---|
| Product Model / Order No. | PXC36.1.D / S55372-C120 |
| Product Line | Siemens Desigo PX (Automation Stations) |
| On-Board Physical I/O Points | 36 Data Points Total:
• 24 Universal Inputs/Outputs (UIO) • 4 Digital Inputs (DI) • 8 Digital Relay Outputs (DO) |
| I/O Signal Capability (UIO) | • Analog In: LG-Ni1000, Ni1000, Pt1000, DC 0–10 V
• Analog Out: DC 0–10 V • Binary Input / Counter (up to 20 Hz) |
| Digital Outputs (DO) | 8 Relay change-over contacts (rated AC 230 V / 2 A) |
| Operating Voltage | AC 24 V ±20% (50/60 Hz) |
| Power Consumption | Max. 35 VA |
| Primary System Bus Communication | BACnet on LonTalk |
| Room Unit Connection Interface | PPS2 interface (supports Siemens QAX.. room units) |
| Local I/O Expansion | TX-I/O Island Bus interface (supports TXM I/O extension modules) |
| Processor & Memory | 133 MHz Freescale processor | 80 MB Total (64 MB SDRAM + 16 MB Flash ROM) |
| RAM / Clock Backup | Field-replaceable AA battery (RAM backup up to 60 days / CR2032 RTC backup up to 10 years) |
| Degree of Protection | IP20 (according to EN 60529) |
| Dimensions (W × H × D) | 293 mm × 176 mm × 77 mm |
Key Advantages
- High Density in Compact Footprint: Houses 36 software-configurable data points directly on the board, minimizing panel space requirements for medium-to-large plant controllers.
- Modular Extendibility: The built-in Island Bus plug enables fast extension via TX-I/O modules (such as TXM1.8U, TXM1.6R) without replacing the main controller.
- Native BACnet Protocol: Ensures open, standardized interoperability over LonTalk field buses across building management platforms.
- Autonomous Intelligence: Executes complex control loops, time schedules, alarm handling, and historical trend logging independently without requiring a constant server connection.
- Flexible Universal Terminals: Software-definable Universal I/O points (UIO) accommodate temperature sensors, 0–10 V signals, status contacts, or analog outputs dynamically.
- PPS2 Room Unit Support: Allows direct point-to-point connection of user-friendly Siemens QAX room control units.
Important Installation & Usage Precautions
- Enclosure Protection: Rated IP20; must be installed inside a clean, dry, lockable control cabinet or enclosure to protect against dust and moisture.
- Power Supply Quality: Operates strictly on AC 24 V (SELV / PELV). Ensure transformer sizing accommodates the 35 VA internal load plus connected active sensor supplies.
- Relay Output Limits: Relay outputs are rated up to 2 A at 230 V AC. Heavy inductive loads (e.g., large motor starters or solenoids) require interposing relays or contactors.
- Island Bus Grounding: When extending with TX-I/O modules via the Island Bus, the system neutral (⊥\bot⊥) terminal must be properly referenced across all expansion blocks.
- Battery Maintenance: Periodically check the internal RAM backup battery (AA type) to prevent program memory loss during extended power outages.
- LonTalk Termination: Ensure the LonTalk fieldbus topology is correctly terminated at both ends with appropriate bus terminators to maintain reliable BACnet communication.
Applications
- Air Handling Units (AHUs): Multi-stage heating/cooling coil control, fan speed regulation (VFD), damper positioning, and filter monitoring.
- Central Heating & Cooling Plants: Sequencing multiple boilers, chillers, primary/secondary pumps, and heat exchangers.
- VAV & District Energy Management: Managing variable air volume systems and thermal energy distribution loops.
- Industrial & Commercial Facilities: Installed in office buildings, hospitals, schools, and shopping centers requiring distributed BACnet building automation.
Shipping Port: Xiamen, China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
Please make an inquiry for more models:
| SIEMENS | 6DD1682-0CH0 |
| SIEMENS | 6DD1683-0CC0 |
| SIEMENS | 6DD1683-0CD0 |
| SIEMENS | 6DD2920-0AB0 |
| SIEMENS | 6DR2001-1 |
| SIEMENS | 6DS1200-8AB |
| SIEMENS | 6DS1206-8AA |
| SIEMENS | 6DS1212-8AB |
| SIEMENS | 6DS1213-8AA |
| SIEMENS | 6DS1311-8AE |
| SIEMENS | 6DS1315-8AC |
| SIEMENS | 6DS1322-8BA |
| SIEMENS | 6DS1412-8DD |
| SIEMENS | 6DS1601-8BA |
| SIEMENS | 6DS1603-8BA |
| SIEMENS | 6DS1618-8CA |
| SIEMENS | 6DS1703-8AB |
| SIEMENS | 6DS1717-8CC |
| SIEMENS | 6DS1722-8BA |
| SIEMENS | 6DS1723-8BA |
| SIEMENS | 6DS1731-8DC |
| SIEMENS | 6DS1731-8RR |
| SIEMENS | 6DD1683-0BC5 |
| SIEMENS | 6DD1600-0AF0 |
| SIEMENS | 9AB4143-2EB23 |
| SIEMENS | 6DD1684-0CC1 |
| SIEMENS | 6DD1684-0CH0 |
| SIEMENS | 6DD1684-0DB2 |
| SIEMENS | 6DD1684-0DG1 |
| SIEMENS | 6DD1684-0DK0 |