Siemens PXC36.1.D Desigo PX Compact Automation Station

 

Product Overview

The Siemens PXC36.1.D (Stock No. S55372-C120) is a high-performance, compact direct digital control (DDC) automation station belonging to the Desigo PX system family.

Designed for HVAC and building services automation, the PXC36.1.D features a fixed physical layout of 36 integrated I/O data points. The “.1” designation indicates that it includes an Island Bus interface, allowing local I/O expansion using TX-I/O modules or TX Open integrations. It operates using native BACnet on LonTalk network protocols for peer-to-peer and supervisory communication.

 

Technical Specifications

Parameter Specification Details
Product Model / Order No. PXC36.1.D / S55372-C120
Product Line Siemens Desigo PX (Automation Stations)
On-Board Physical I/O Points 36 Data Points Total:

• 24 Universal Inputs/Outputs (UIO)

• 4 Digital Inputs (DI)

• 8 Digital Relay Outputs (DO)

I/O Signal Capability (UIO) • Analog In: LG-Ni1000, Ni1000, Pt1000, DC 0–10 V

• Analog Out: DC 0–10 V

• Binary Input / Counter (up to 20 Hz)

Digital Outputs (DO) 8 Relay change-over contacts (rated AC 230 V / 2 A)
Operating Voltage AC 24 V ±20% (50/60 Hz)
Power Consumption Max. 35 VA
Primary System Bus Communication BACnet on LonTalk
Room Unit Connection Interface PPS2 interface (supports Siemens QAX.. room units)
Local I/O Expansion TX-I/O Island Bus interface (supports TXM I/O extension modules)
Processor & Memory 133 MHz Freescale processor | 80 MB Total (64 MB SDRAM + 16 MB Flash ROM)
RAM / Clock Backup Field-replaceable AA battery (RAM backup up to 60 days / CR2032 RTC backup up to 10 years)
Degree of Protection IP20 (according to EN 60529)
Dimensions (W × H × D) 293 mm × 176 mm × 77 mm

 

Key Advantages

  • High Density in Compact Footprint: Houses 36 software-configurable data points directly on the board, minimizing panel space requirements for medium-to-large plant controllers.
  • Modular Extendibility: The built-in Island Bus plug enables fast extension via TX-I/O modules (such as TXM1.8U, TXM1.6R) without replacing the main controller.
  • Native BACnet Protocol: Ensures open, standardized interoperability over LonTalk field buses across building management platforms.
  • Autonomous Intelligence: Executes complex control loops, time schedules, alarm handling, and historical trend logging independently without requiring a constant server connection.
  • Flexible Universal Terminals: Software-definable Universal I/O points (UIO) accommodate temperature sensors, 0–10 V signals, status contacts, or analog outputs dynamically.
  • PPS2 Room Unit Support: Allows direct point-to-point connection of user-friendly Siemens QAX room control units.

 

Important Installation & Usage Precautions

  • Enclosure Protection: Rated IP20; must be installed inside a clean, dry, lockable control cabinet or enclosure to protect against dust and moisture.
  • Power Supply Quality: Operates strictly on AC 24 V (SELV / PELV). Ensure transformer sizing accommodates the 35 VA internal load plus connected active sensor supplies.
  • Relay Output Limits: Relay outputs are rated up to 2 A at 230 V AC. Heavy inductive loads (e.g., large motor starters or solenoids) require interposing relays or contactors.
  • Island Bus Grounding: When extending with TX-I/O modules via the Island Bus, the system neutral (⊥\bot⊥) terminal must be properly referenced across all expansion blocks.
  • Battery Maintenance: Periodically check the internal RAM backup battery (AA type) to prevent program memory loss during extended power outages.
  • LonTalk Termination: Ensure the LonTalk fieldbus topology is correctly terminated at both ends with appropriate bus terminators to maintain reliable BACnet communication.

 

Applications

  • Air Handling Units (AHUs): Multi-stage heating/cooling coil control, fan speed regulation (VFD), damper positioning, and filter monitoring.
  • Central Heating & Cooling Plants: Sequencing multiple boilers, chillers, primary/secondary pumps, and heat exchangers.
  • VAV & District Energy Management: Managing variable air volume systems and thermal energy distribution loops.
  • Industrial & Commercial Facilities: Installed in office buildings, hospitals, schools, and shopping centers requiring distributed BACnet building automation.

Shipping Port: Xiamen, China

Payment: Bank of Chicago, Bank of Singapore

Express cooperation: fedex, DHL, UPS and your express account

Service: Professional Sales provides 24 hours /7 days online service

Please make an inquiry for more models:

SIEMENS 6DD1682-0CH0
SIEMENS 6DD1683-0CC0
SIEMENS 6DD1683-0CD0
SIEMENS 6DD2920-0AB0
SIEMENS 6DR2001-1
SIEMENS 6DS1200-8AB
SIEMENS 6DS1206-8AA
SIEMENS 6DS1212-8AB
SIEMENS 6DS1213-8AA
SIEMENS 6DS1311-8AE
SIEMENS 6DS1315-8AC
SIEMENS 6DS1322-8BA
SIEMENS 6DS1412-8DD
SIEMENS 6DS1601-8BA
SIEMENS 6DS1603-8BA
SIEMENS 6DS1618-8CA
SIEMENS 6DS1703-8AB
SIEMENS 6DS1717-8CC
SIEMENS 6DS1722-8BA
SIEMENS 6DS1723-8BA
SIEMENS 6DS1731-8DC
SIEMENS 6DS1731-8RR
SIEMENS 6DD1683-0BC5
SIEMENS 6DD1600-0AF0
SIEMENS 9AB4143-2EB23
SIEMENS 6DD1684-0CC1
SIEMENS 6DD1684-0CH0
SIEMENS 6DD1684-0DB2
SIEMENS 6DD1684-0DG1
SIEMENS 6DD1684-0DK0