Schneider QO120VSC10 Miniature Circuit Breaker
Product Overview
The Schneider Electric / Square D QO120VSC10 is a 1-pole (single-pole), 20-amp miniature circuit breaker (MCB) from the QOvs series. Built according to international standards (IEC/EN 60898-1), it provides thermal-magnetic protection against overloads and short circuits in sub-distribution boards and consumer units.
Equipped with a C Tripping Curve and a 10 kA breaking capacity, it is specifically designed to handle moderate inrush currents while safeguarding electrical wiring and connected equipment.
Technical Specifications
| Parameter | Specification Details |
| Product Model | QO120VSC10 |
| Product Series | Square D QOvs |
| Device Type | Miniature Circuit Breaker (MCB) |
| Number of Poles | 1-Pole (1P) |
| Rated Current (I_n) | 20 A |
| Tripping Curve | C Curve (Tripping threshold: 5 \times I_n to 10 \times I_n) |
| Rated Operational Voltage (U_e) | 240 / 415 V AC (50/60 Hz) |
| Short-Circuit Breaking Capacity (I_{cn}) | 10,000 A (10 kA) @ 240 V AC (IEC/EN 60898-1) |
| Rated Service Breaking Capacity (I_{cs}) | 7.5 kA (75% of I_{cn}) |
| Rated Insulation Voltage (U_i) | 500 V AC |
| Rated Impulse Withstand Voltage (U_{imp}) | 4 kV |
| Mounting / Terminal Type | Plug-in busbar connection (Top) / Tunnel terminal (Bottom) |
| Connectable Cable Capacity | 1 mm^2 to 25 mm^2 (solid or flexible copper) |
| Degree of Protection | IP20 (IP40 inside enclosure) |
| Operating Temperature | -5 °C to +60 °C |
| Standards & Compliance | IEC/EN 60898-1, RoHS compliant, Halogen-free |
Key Advantages
- Reliable 10 kA Fault Protection: High short-circuit breaking capacity ensures reliable safety even in distribution systems with high fault levels.
- C-Curve Versatility: Ideal for commercial and light-industrial loads, offering high resistance to nuisance tripping caused by initial startup surges.
- Plug-In Busbar Design: Feature-rich QO-style plug-in busbar mounting allows quick, safe, and tool-less snap-fit installation onto compatible distribution boards.
- Visi-Trip / Contact Position Indicator: Built-in mechanical contact position indicator provides instant visual indication of breaker state and trip status.
- High-Quality Terminals: Supports wide wire cross-sections (up to 25 mm^2) for easy, secure, and vibration-resistant wiring.
Important Usage & Installation Precautions
- Distribution Board Compatibility: Ensure the load center or panelboard accepts Square D QOvs series plug-in circuit breakers. Do not force the breaker onto incompatible DIN-rail or screw-fixed systems.
- Terminal Tightening Torque: Always torque the bottom connection terminals to the recommended specification (2 N·m) to prevent loose connections, overheating, or arcing.
- Selective Coordination & Curve Selection: C-curve breakers trip at 5 to 10 times rated current. Verify that upstream main breakers and downstream loads are properly coordinated to avoid unnecessary total power loss.
- Environmental Limits: Operating ambient temperature ranges from -5 °C to +60 °C. De-rate nominal current capacity if installed in switchboards operating at elevated internal temperatures.
- De-energize Before Maintenance: Always isolate incoming power to the distribution board before installing, removing, or servicing the circuit breaker.
Applications
- Commercial Power Distribution: Protecting 20 A branch circuits in retail spaces, offices, schools, and hospitals.
- Small Motor & Inductive Loads: Safeguarding HVAC equipment, small pumps, blowers, and air compressors subject to moderate starting surges.
- Industrial Auxiliary Circuits: Supplying power to control panels, utility outlets, and auxiliary lighting circuits in factories.
- Lighting Systems: Protection for high-intensity discharge (HID) and LED commercial lighting arrays with high initial inrush current requirements.
Shipping Port: Xiamen, China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
Please make an inquiry for more models:
| SCHNEIDER | 140CPU43412AC |
| SCHNEIDER | 140CPU43412U |
| SCHNEIDER | 140CPU43412UC |
| SCHNEIDER | 140CPU53414BC |
| SCHNEIDER | 140CPU65260C |
| SCHNEIDER | 140CPU65160C |
| SCHNEIDER | 140CHS11000C |
| SCHNEIDER | 140CHS21000C |
| SCHNEIDER | BMXDDI1602 |
| SCHNEIDER | BMXDDO1602 |
| SCHNEIDER | BMXAMI0810 |
| SCHNEIDER | BMXAMO0802 |
| SCHNEIDER | BMH2052P11A2A |
| SCHNEIDER | BMXDAO1605 |
| SCHNEIDER | BMXCPS3020 |
| SCHNEIDER | BMXDDO6402K |
| SCHNEIDER | BMXP342020H |
| SCHNEIDER | BMXEHC0800 |
| SCHNEIDER | BMXAMO0410 |
| SCHNEIDER | BMXXBP1200 |
| SCHNEIDER | 140CRA21120 |
| SCHNEIDER | 140ERT85420 |
| SCHNEIDER | 140N0E77100 |
| SCHNEIDER | 140NOC78000 |
| SCHNEIDER | 140NRP95400 |
| SCHNEIDER | 140SDI95300S |
| SCHNEIDER | 140SDO95300S |
| SCHNEIDER | TSXP57303AM |
| SCHNEIDER | 416NHM30032A |
| SCHNEIDER | 416NHM30030A |