Description

Schneider 59715/MES120 I/O Module

The Schneider Electric 59715 MES120 is an expansion I/O module designed for Sepam Series 60 and Series 80 digital protection relays. It adds 14 digital logic inputs and 6 relay outputs across a 24 V to 250 V DC input range.

 

Product Overview

  • Primary Role: Expands the binary input and output capacity of Sepam Series 60 and Series 80 protection relay base units.
  • Input/Output Mix: Combines 14 potential-free DC logic inputs with 1 control relay output (for breaker tripping or closing) and 5 annunciation relay outputs (for alarms and status signaling).
  • Configuration: Inputs and outputs map directly to predefined control functions or custom logic equations inside the Sepam SFT2841 configuration software.

 

Technical Specifications

  • Part Number / Model: 59715 / MES120
  • Compatible Base Units: Sepam Series 60 and Series 80 (up to 3 modules per base unit)
  • Logic Inputs: 14 channels, 24 V to 250 V DC nominal (19.2 V to 275 V DC operating range; 3 mA typical draw; 14 V switching threshold)
  • Relay Outputs: 6 total — 1 control relay and 5 annunciation relays
  • Control Relay Rating: 8 A continuous at 48 V DC (making capacity < 15 A for 200 ms)
  • Annunciation Relay Rating: 2 A continuous at 100–240 V AC or 127 / 220 V DC
  • Terminal Wire Capacity: Screw-type connectors accepting 1 wire (0.2–2.5 mm²) or 2 wires (0.2–1 mm²)
  • Dimensions (H × W × D): 170 mm × 40 mm × 120 mm
  • Net Weight: 0.38 kg
  • Operating Temperature: -25 °C to +70 °C
  • Mechanical & EMC Standards: IEC 60255-21-1/2/3 (vibration, shock, seismic Level 2) and IEC 60255-22-1 / ANSI C37.90.1

 

Key Advantages

  • Wide Input Voltage Flexibility: A single module accepts 24 V to 250 V DC auxiliary control voltages, simplifying spare-parts stocking across substations with mixed battery banks.
  • Scalable I/O Expansion: You can stack up to three MES120 modules on one Sepam base unit, scaling up to 42 extra inputs and 18 extra outputs without adding external PLCs.
  • Substation-Grade Immunity: Meets IEC 60255 and ANSI C37.90.1 surge, fast-transient, and seismic standards to prevent false trips in high-voltage switchgear.
  • Plug-In Rear Mounting: Docks directly onto the rear connectors of the Sepam base unit, keeping panel cutouts unchanged.

 

Important Installation & Usage Precautions

  • Strict Mounting Order: Install modules sequentially on the base unit’s rear connectors—use H1 for one module, H1 and H2 for two, and H1, H2, and H3 for three.
  • External DC Supply Required: The 14 logic inputs are potential-free and require an external DC wetting power supply.
  • Disconnect Before Hi-Pot Testing: Always disconnect all input and output wiring before running dielectric (Hi-Pot) or Megger insulation tests on the switchgear panel to avoid damaging internal electronics.
  • De-Energize & Tighten Unused Terminals: Turn off all power (including backfed auxiliary circuits) before installation, and tighten every screw terminal—even unused ones—to prevent vibration loosening.
  • Not Compatible with Series 20/40: Only works with Sepam Series 60 and Series 80 base units (Series 20 and 40 use MES114 modules instead).

 

Applications

  • Medium- & High-Voltage Switchgear: Monitors circuit breaker and disconnector auxiliary contacts while issuing trip/close commands.
  • Transformer & Feeder Bays: Collects Buchholz relay, oil temperature, and pressure alarms for local annunciation and SCADA transmission.
  • Industrial Power Substations & Generators: Handles complex interlocking logic, load-shedding schemes, and busbar transfer automation in utilities, oil and gas, and heavy manufacturing.

 

Verdict

Choose the Schneider Electric 59715 MES120 if you need to expand digital I/O on a Sepam Series 60 or 80 relay using a 24–250 V DC control supply. Skip it if you run a Sepam Series 20/40 relay or need the MES120G / MES120H variants designed specifically for higher pick-up threshold voltages in noisy 110–250 V DC circuits.

Shipping Port: Xiamen, China

Payment: Bank of Chicago, Bank of Singapore

Express cooperation: fedex, DHL, UPS and your express account

Service: Professional Sales provides 24 hours /7 days online service

Please make an inquiry for more models:

SCHNEIDER 140CPU43412AC
SCHNEIDER 140CPU43412U
SCHNEIDER 140CPU43412UC
SCHNEIDER 140CPU53414BC
SCHNEIDER 140CPU65260C
SCHNEIDER 140CPU65160C
SCHNEIDER 140CHS11000C
SCHNEIDER 140CHS21000C
SCHNEIDER BMXDDI1602
SCHNEIDER BMXDDO1602
SCHNEIDER BMXAMI0810
SCHNEIDER BMXAMO0802
SCHNEIDER BMH2052P11A2A
SCHNEIDER BMXDAO1605
SCHNEIDER BMXCPS3020
SCHNEIDER BMXDDO6402K
SCHNEIDER BMXP342020H
SCHNEIDER BMXEHC0800
SCHNEIDER BMXAMO0410
SCHNEIDER BMXXBP1200
SCHNEIDER 140CRA21120
SCHNEIDER 140ERT85420
SCHNEIDER 140N0E77100
SCHNEIDER 140NOC78000
SCHNEIDER 140NRP95400
SCHNEIDER 140SDI95300S
SCHNEIDER 140SDO95300S
SCHNEIDER TSXP57303AM
SCHNEIDER 416NHM30032A
SCHNEIDER 416NHM30030A